Philippines

Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

variable speed drive ATV610 - 1.5 kW / 2HP - 380...415 V - IP20

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Altivar Easy 610
    product or component type
    Variable speed drive
    product specific application
    Fan, pump, compressor, conveyor
    device short name
    ATV610
    variant
    Standard version
    product destination
    Asynchronous motors
    mounting mode
    Cabinet mount
    EMC filter
    Integrated conforming to EN/IEC 61800-3 category C3 with 50 m maximum
    IP degree of protection
    IP20
    type of cooling
    Forced convection
    supply frequency
    50...60 Hz (+/-5 %)
    network number of phases
    3 phases
    [Us] rated supply voltage
    380...415 V (- 15...10 %)
    motor power kW
    1.5 kW normal duty
    0.75 kW heavy duty
    motor power hp
    2 hp normal duty
    1 hp heavy duty
    line current
    5.7 A at 380 V normal duty
    5.3 A at 415 V normal duty
    3.1 A at 380 V heavy duty
    2.8 A at 415 V heavy duty
    prospective line Isc
    5 kA
    apparent power
    3.8 kVA at 415 V normal duty
    2 kVA at 415 V heavy duty
    continuous output current
    4 A at 4 kHz normal duty
    2.2 A at 4 kHz heavy duty
    maximum transient current
    4.4 A during 60 s normal duty
    3.3 A during 60 s heavy duty
    asynchronous motor control profile
    Constant torque standard
    Variable torque standard
    Optimized torque mode
    output frequency
    0.0001...0.5 kHz
    nominal switching frequency
    4 kHz
    switching frequency
    2...12 kHz adjustable
    number of preset speeds
    16 preset speeds
    communication port protocol
    Modbus serial
    option card
    Slot A : communication card Profibus DP V1
    Slot A : digital or analog I/O extension card
    Slot A : relay output card
    Complementary
    output voltage
    <= power supply voltage
    motor slip compensation
    Adjustable
    Automatic whatever the load
    Can be suppressed
    Not available in permanent magnet motor law
    acceleration and deceleration ramps
    Linear adjustable separately from 0.01 to 9000 s
    S, U or customized
    braking to standstill
    By DC injection
    protection type
    Motor : thermal protection
    Motor : motor phase break
    Drive : thermal protection
    Drive : overheating
    Drive : overcurrent between output phases and earth
    Drive : overload of output voltage
    Drive : short-circuit protection
    Drive : motor phase break
    Drive : overvoltages on the DC bus
    Drive : line supply overvoltage
    Drive : line supply undervoltage
    Drive : line supply phase loss
    Drive : overspeed
    Drive : break on the control circuit
    frequency resolution
    Display unit : 0.1 Hz
    Analog input : 0.012/50 Hz
    electrical connection
    Control, screw terminal : 0.5...1.5 mm²
    Line side, screw terminal : 2.5...16 mm²
    Motor, screw terminal : 2.5...16 mm²
    connector type
    1 RJ45 (on the remote graphic terminal) for Modbus serial
    physical interface
    2-wire RS 485 for Modbus serial
    transmission frame
    RTU for Modbus serial
    transmission rate
    4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
    type of polarization
    No impedance for Modbus serial
    number of addresses
    1...247 for Modbus serial
    method of access
    Slave
    supply
    External supply for digital inputs : 24 V DC (limits : 19...30 V), <= 1.25 mA (overload and short-circuit protection)
    Internal supply for reference potentiometer (1 to 10 kOhm) : 10.5 V DC +/- 5 %, <= 10 mA (overload and short-circuit protection)
    local signalling
    1 LED red for presence of voltage
    2 LEDs for local diagnostic
    1 LED yellow for embedded communication status
    2 LEDs dual colour for communication module status
    width
    145 mm
    height
    297 mm
    350 mm with EMC plate
    depth
    203 mm
    product weight
    2.4 kg
    analogue input number
    3
    analogue input type
    Software-configurable voltage AI1, AI2, AI3 : 0...10 V DC, impedance 30 kOhm, resolution 12 bits
    Software-configurable current AI1, AI2, AI3 : 0...20 mA, impedance 250 Ohm, resolution 12 bits
    Software-configurable temperature probe or water level sensor AI2, AI3
    discrete input number
    6
    discrete input type
    Programmable as pulse input DI5, DI6 0...30 kHz : 24 V DC (limits : <= 30 V)
    Programmable as logic input DI1...DI6 : 24 V DC (limits : <= 30 V), impedance 3.5 kOhm
    input compatibility
    Level 1 PLC conforming to EN/IEC 61131-2, logic input DI1...DI6
    Level 1 PLC conforming to IEC 65A-68, pulse input DI5, DI6
    discrete input logic
    Positive logic (source) : DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)
    Negative logic (sink) : DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)
    Positive logic (source) : DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
    analogue output number
    2
    analogue output type
    Software-configurable current AQ1, AQ2 : 0...20 mA, resolution 10 bits
    Software-configurable voltage AQ1, AQ2 : 0...10 V DC,impedance 470 Ohm, resolution 10 bits
    sampling duration
    Analog input AI1, AI2, AI3 : 5 ms (+/- 0.1 ms)
    Analog output AQ1, AQ2 : 10 ms (+/- 1 ms)
    Discrete input DI1...DI6 : 2 ms (+/- 0.5 ms) configurable
    Pulse input DI5, DI6 : 5 ms (+/- 1 ms) configurable
    accuracy
    Analog input AI1, AI2, AI3 : +/- 0.6 % for a temperature variation 60 °C
    Analog output AQ1, AQ2 : +/- 1 % for a temperature variation 60 °C
    linearity error
    Analog input AI1, AI2, AI3 : +/- 0.15 % of maximum value
    Analog output AQ1, AQ2 : +/- 0.2 %
    relay output number
    3
    relay output type
    Configurable relay logic R1 : fault relay NO/NC, electrical durability 100000 cycles
    Configurable relay logic R2 : sequence relay NO, electrical durability 100000 cycles
    Configurable relay logic R3 : sequence relay NO, electrical durability 100000 cycles
    refresh time
    Relay output R1, R2, R3 : 5 ms (+/- 0.5 ms)
    minimum switching current
    Relay output R1, R2, R3 : 5 mA at 24 V DC
    maximum switching current
    Relay output R1, R2, R3 on resistive load (cos phi = 1 : 3 A at 250 V AC
    Relay output R1, R2, R3 on resistive load (cos phi = 1 : 3 A at 30 V DC
    Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at 250 V AC
    Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at 30 V DC
    isolation
    Between power and control terminals
    insulation resistance
    > 1 mOhm at 500 V DC for 1 minute to earth
    Environment
    noise level
    55 dB conforming to 86/188/EEC
    power dissipation in W
    40 W (forced convection) at 380 V, switching frequency 4 kHz
    25 W (natural convection) at 380 V, switching frequency 4 kHz
    operating position
    Vertical +/- 10 degree
    electromagnetic compatibility
    1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
    Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
    Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
    Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
    pollution degree
    2 conforming to EN/IEC 61800-5-1
    vibration resistance
    1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6
    1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn during 11 ms conforming to IEC 60068-2-27
    relative humidity
    5...95 % without condensation conforming to IEC 60068-2-3
    ambient air temperature for operation
    -15...45 °C without derating
    45...60 °C with derating factor
    operating altitude
    1000...4800 m with current derating 1 % per 100 m
    <= 1000 m without derating
    environmental characteristic
    Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
    Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
    standards
    EN/IEC 61800-3
    EN/IEC 61800-3 environment 2 category C3
    EN/IEC 61800-5-1
    IEC 60721-3
    product certifications
    REACH
    marking
    CE
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
  • Documents and Downloads

    Language
    • English
    • Chinese
    Catalogue
    Date
    Size
    Add to My Documents
    Catalog Altivar Easy 610 (Version 5.0)
    Date 8/13/18
    Size 2.4 MB
    User guide
    Date
    Size
    Add to My Documents
    2) ATV610 Installation manual (Version 06.1)
    Date 10/30/18
    Size 4.9 MB
    ATV610 PROFIBUS DP Manual - VW3A3607 (Version 01)
    3) ATV610 Programming Manual (Version 04)
    Date 6/7/17
    Size 4.7 MB
    1) ATV610 Getting started (Version 04)
    Date 10/18/16
    Size 1.1 MB
    ATV610 Modbus manual (Version 01)
    Date 12/1/15
    Size 4.5 MB
    Certificate
    Date
    Size
    Add to My Documents
    ATV610 EU DECLARATION (Version 1.0)
    Date 5/29/18
    Size 576.3 KB
    ATV6XX-BACNET-CERTIFICATE (Version 1.0)
    Date 2/14/19
    Size 695.9 KB
    End of Life Information
    Date
    Size
    Add to My Documents
    ALTIVAR 610 - Size 1 - 0.75 to 7.5kW - 3PH - 380/415V, Product End-of-Life Instructions (Version 2.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    ALTIVAR 610 - Size 1 - 0.75 to 7.5kW - 3PH - 380/415V, Product Environmental Profile (Version 2.0)
    Instruction Sheet: China RoHS - Hazardous Substances Table (Version 01)
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions
    IP20 Drives


    Drawings from left to right: rear view, right side view with top cover, right side view without top cover.

    IP20 Drives With EMC Plate


    Drawings from left to right: rear view, right side view with top cover.


  • Mounting and Clearance

    Clearances


    X1

    X2

    X3

    ≥ 100 mm (3.94 in.)

    ≥ 100 mm (3.94 in.)

    ≥ 10 mm (0.39 in.)

    • Mount the device in a vertical position (±10°). This is required for cooling the device.

    • Do not mount the device close to heat sources.

    • Leave sufficient free space so that the air required for cooling purposes can circulate from the bottom to the top of the drive.


    Mounting Types
    Mounting Type A: Individual IP21


    a ≥ =
    100 mm (3.94 in.)

    Mounting Type B: Side by Side IP20



  • Connections and Schema

    Single or Three-phase Power Supply - Diagram With Line Contactor


    (1)
    Line chokes
    (2)
    See control block wiring diagram
    A1 :
    Drive
    KM1 :
    Line Contactor
    Q2, Q3 :
    Circuit breakers
    S1, S2 :
    Pushbuttons
    T1 :
    Transformer for control part


    Control Block Wiring Diagram


    (1)
    Digital Input
    (2)
    Analog Output
    (3)
    Analog Input
    R1A, R1B, R1C :
    Fault relay output
    R2A, R2C :
    Sequence relay output
    R3A, R3C :
    Sequence relay output

    Sensor Connection

    It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.



  • Performance Curves

    Derating Curves


    In :
    Nominal Drive Current
    SF :
    Switching Frequency